3.3.4 Control Lines And Signal Lines Between Master Control Unit And
Amplifier
For the definition of the speed reference, the master control unit normally provides an
output of a digital/analogue converter. This output signal normally is measured against
ground or against reference voltage. The input at the amplifier is a differential input with set
value+ at 4d and set value- at 4b. The lines at these inputs have to be run to the control unit
in the same cable. This cable has to be shielded, with connection of the shield to the servo
amplifier and the control unit. Input+ of the TBF-R is connected to the set value output of the
master control unit. Input- of the TBF-R is connected to the reference point for the set value
output at the master control unit.
The lines Iext., Int.off, Ready output, Enable and Pos.Stop/Neg.Stop, if used, have to be
wired in a shielded cable as well. These lines are measured against ground, that means
the connection requested in 0. between TBF and master control unit is sufficient.
3.3.5 The Simulated Incremental Encoder Signals
The connection cable for the incremental encoder signals has to be shielded. The pairs
track A+/track A-, track B+/track B- and track I+/track I- have to be twisted, the shorter the
twist the better the interference immunity. Each pair is shielded separately within the total
shield (see 0). The shield has to be connected on amplifier side and control unit side.